NEC 440 Heat Pump & HVAC Circuit Sizing Calculator

MCA & MOP Wire Gauge, Breaker / Fuse, EGC (Table 250.122), Disconnect & Voltage Drop

100% Client-Side
Presets:
Step 1NEC 440.32 & 440.22

Equipment Nameplate Ratings (MCA & MOP)

A

Determines minimum wire size (AWG) per NEC 440.32.

A

Determines max breaker/fuse size & EGC (Table 250.122).

Step 2NEC Table 310.16 & 250.122

Wiring Method & One-Way Run Length

Applicable table: NEC 334.80 / Table 310.16 (60°C)

ft

Used to verify <= 3% voltage drop at MCA (NEC 250.122(B)).

14 AWG Cu • 25A 2P • EGC 10 AWG Cu

Frequently Asked Questions — NEC Article 440 HVAC Circuit Sizing

Key NEC 440, 240.4(G), Table 310.16, and Table 250.122 rules for heat pumps, mini-splits, and A/C condensers.

Under NEC 240.4(G) and Article 440, air-conditioning and heat pump compressor circuits are explicitly exempt from the NEC 240.4(D) small-conductor 15A/20A/30A breaker cap. You size the wire to the nameplate MCA (Minimum Circuit Ampacity, e.g., 18A -> 12 AWG Cu @ 20A) and size the breaker up to the nameplate MOP (Maximum Overcurrent Protection, e.g., 30A) so the breaker handles compressor startup inrush current while the unit’s internal overload relay protects the wire.