NEC 440 Heat Pump & HVAC Circuit Sizing Calculator
MCA & MOP Wire Gauge, Breaker / Fuse, EGC (Table 250.122), Disconnect & Voltage Drop
Equipment Nameplate Ratings (MCA & MOP)
Determines minimum wire size (AWG) per NEC 440.32.
Determines max breaker/fuse size & EGC (Table 250.122).
Wiring Method & One-Way Run Length
Applicable table: NEC 334.80 / Table 310.16 (60°C)
Used to verify <= 3% voltage drop at MCA (NEC 250.122(B)).
Frequently Asked Questions — NEC Article 440 HVAC Circuit Sizing
Key NEC 440, 240.4(G), Table 310.16, and Table 250.122 rules for heat pumps, mini-splits, and A/C condensers.
Under NEC 240.4(G) and Article 440, air-conditioning and heat pump compressor circuits are explicitly exempt from the NEC 240.4(D) small-conductor 15A/20A/30A breaker cap. You size the wire to the nameplate MCA (Minimum Circuit Ampacity, e.g., 18A -> 12 AWG Cu @ 20A) and size the breaker up to the nameplate MOP (Maximum Overcurrent Protection, e.g., 30A) so the breaker handles compressor startup inrush current while the unit’s internal overload relay protects the wire.