Subpanel & ADU Feeder Wire Size Calculator
NEC 310.16, 310.12 (83% Rule), 250.122(B) Voltage Drop & 250.32 Detached Structure Checklist
Presets:
Step 1NEC 310.16 & 310.12
Subpanel Breaker, Conductor Material & Wiring Method
Step 2NEC 215.2 & 250.122(B)
Run Length & Design Load for Voltage Drop
ft
A
Defaults to 80% of feeder breaker (80A).
100A: 1 AWG Al • EGC 6 AWG Al (1.7% VD)
Frequently Asked Questions — Subpanel & ADU Feeder Sizing
Key NEC 310.16, 310.12 (83% rule), 250.122(B), and 250.32 rules for garages, workshops, and ADUs.
No—under NEC Table 310.16 (75°C column), 2 AWG Aluminum is rated for 90A maximum. The 83% residential sizing rule (NEC 310.12) that allows 2 AWG Aluminum on a 100A breaker applies ONLY when the feeder carries the ENTIRE load of a dwelling unit (such as a standalone ADU), NOT a garage or workshop subpanel. For a standard garage/shop subpanel, either use 1 AWG Aluminum for a full 100A breaker, or protect 2 AWG Aluminum with a 90A breaker.