Subpanel & ADU Feeder Wire Size Calculator

NEC 310.16, 310.12 (83% Rule), 250.122(B) Voltage Drop & 250.32 Detached Structure Checklist

100% Client-Side
Presets:
Step 1NEC 310.16 & 310.12

Subpanel Breaker, Conductor Material & Wiring Method

Step 2NEC 215.2 & 250.122(B)

Run Length & Design Load for Voltage Drop

ft
A

Defaults to 80% of feeder breaker (80A).

100A: 1 AWG Al • EGC 6 AWG Al (1.7% VD)

Frequently Asked Questions — Subpanel & ADU Feeder Sizing

Key NEC 310.16, 310.12 (83% rule), 250.122(B), and 250.32 rules for garages, workshops, and ADUs.

No—under NEC Table 310.16 (75°C column), 2 AWG Aluminum is rated for 90A maximum. The 83% residential sizing rule (NEC 310.12) that allows 2 AWG Aluminum on a 100A breaker applies ONLY when the feeder carries the ENTIRE load of a dwelling unit (such as a standalone ADU), NOT a garage or workshop subpanel. For a standard garage/shop subpanel, either use 1 AWG Aluminum for a full 100A breaker, or protect 2 AWG Aluminum with a 90A breaker.